MC-1260a

Parameter MC-1260a
Model / Series MC-1260a (Metasol series)
Main contacts 3 × NO (3P)
Auxiliary contacts 2 NO + 2 NC (2a2b) integrated
Rated current (AC-3) 1260 A
Coil/control voltage AC100–240 V / DC100–220 V (50/60 Hz)
Rated operational voltage (Ue) Up to 690 V (IEC 60947-4-1)
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand (Uimp) 8 kV
Dimensions (W×H×D) ~398 × 470 × 373 mm.
Mounting Panel/bolt mount, bottom cable or bar connection.
Standards / Certifications IEC 60947-4-1, UL 508, CE, CCC, marine type approvals (KR, LR, DNV)
at 1260 A, this unit’s terminals accept bolted copper bars, not wire lugs. Use torque-rated bolts, proper creepage clearance, and verify coil control supply before energizing

Description

LS Electric Metasol; MC-1260a (AC100–240V/DC100–220V Coil, 2a2b Aux)

A robust, heavy-frame contactor engineered for high-power three-phase systems up to 1260 A. The MC-1260a offers high breaking capacity, arc-resistant chambers, and modular terminals suited for copper-bar or lug termination.

The Polar Energy Assessment:

This isn’t panel candy; it’s for serious power distribution and motor-control work. The MC-1260a combines LS Electric’s standard Metasol design with the contact reliability, arc-quenching, and coil endurance demanded by continuous-duty industrial loads. With proper upstream protection and thermal coordination, it can handle motor feeders, capacitor banks, and heavy compressors without breaking a sweat.

Pros

  • Rated 1260 A (AC-3); ideal for large-frame motors, MCCs, and power feeders.
  • Universal coil (AC100–240 V / DC100–220 V) simplifies stock and wiring.
  • Arc-chamber design extends electrical life and improves safety under high-current switching.
  • Compatible with LS accessories; mechanical interlocks, thermal overloads, auxiliary blocks.

Limitations

  • Extremely heavy (≈ 35 kg+); requires fixed panel or frame mount.
  • Bolt mount only.
  • Noise and coil inrush at startup; design around control-circuit loading.

Typical use cases

  • Main feeders or large-motor starters in heavy industrial MCCs.
  • Power switching for chillers, compressors, or pump stations.
  • Backup generator transfer and large-scale HVAC or energy systems.
  • Busbar-based distribution panels requiring 1 kA+ contactors.