Parameter LSLV0040S100-2EONNS /
Model / Series LSLV0040S100-2EONNS / S100 Series
Rated motor power HD: 4.0 kW / ND: 5.5 kW (≈ 5.4 hp / 7.5 hp)
Input voltage 3-phase 200–240 VAC
Output 3-phase 200–240 VAC, 0–400 Hz
Rated output current HD: 17.0 A · ND: 18.0 A
Output frequency 0–400 Hz
Mounting Side-by-side in control panel / enclosure
Enclosure / Protection IP20 (UL Type 1 optional)
EMC filter Check datasheet
Communications Built-in: Modbus RTU, LS INV 485; Options: Profinet, EtherNet/IP, CANopen, Profibus-DP
Certifications KC, CE, UL, cULized standards
Ambient temp HD: –10 to +50 °C · ND: –10 to +40 °C
Dimensions (approx.) Frame C: 140 × 128 × 145 mm (W × H × D)

Buy Now

Description

LS Electric LSLV0040S100-2EONNS Inverter VFD (S100 — Standard Drive)

Three-phase input / three-phase output standard drive (S100 series) by LS Electric, offering general-purpose control with dual torque ratings and typical features for mid-power motor drives.

The Polar Energy Assessment:

The LSLV0040S100-2EONNS sits in the mid-power range. It handles a 4.0 kW (HD) to 5.5 kW (ND) class motor, supports V/f, sensorless vector, and built-in communications. It’s solid for industrial automation, HVAC, pumps, fans — but be sure to house it in a cabinet when there’s dust, humidity, or mechanical strain, because of its IP20 rating.

Pros

  • Dual torque ratings (Heavy Duty & Normal Duty) for load flexibility.
  • Supports common control methods: V/f, slip compensation, sensorless vector, and PM sensorless.
  • Built-in Modbus RTU (LS INV 485) plus optional fieldbus (Profinet, EtherNet/IP, CANopen, Profibus-DP).
  • Overload capacity: 150 % for 1 min (HD), 120 % for 1 min (ND).
  • Compact form factor (Frame C) suitable for panel installation.
  • Standard compliance: KC, CE, UL, cUL.

Limitations

  • No built-in EMC filter on the “2EONNS” variant.
  • Enclosure protection: IP20 — vulnerable to dust, moisture, and outdoor conditions.
  • At high altitudes or extreme temperature, derating required (spec says derate 1 % per 100 m above 1,000 m).

Typical use cases

  • Industrial pumps, fans, blowers in manufacturing plants.
  • HVAC systems in large buildings.
  • Conveyor drives, machine tools in mid-power ranges.
  • OEM systems that require moderate power and reliable drive control functions.