LS Electric LSLV0022H100-2CONN(Plus) Inverter VFD Low Voltage Drive

Parameter LSLV0022H100-2CONN(PLUS)
Model / Series LSLV0022H100-2CONN(PLUS) / H100+ Series
Rated motor power HD: 1.5 kW (2 hp) · ND: 2.2 kW (3 hp)
Input voltage 3-phase 200–240 VAC
Output 3-phase 200–240 VAC, variable up to 400 Hz
Rated output current HD: 8 A · ND: 12 A
Output frequency 0–400 Hz
Mounting Cabinet / panel mounting (side-by-side installation inside enclosure)
Enclosure / Protection IP20 (UL Type 1 optional)
EMC filter Check datasheet
Communications Modbus RTU, LS INV 485, BACnet MSTP, LonWorks, Metasys N2 built-in; optional: RAPIEnet+, EtherNet/IP, Modbus TCP, BACnet/IP
Certifications / Standards KC, CE, UL, cUL
Ambient temp HD: –10 to +50 °C · ND: –10 to +40 °C (derate at elevated altitude)
Dimensions (approx.) Frame A: 160 × 232 × 181 mm (W × H × D)
Other Features 5 relay outputs, 1 open-collector output, analog/digital I/O terminals

Buy Now

Description

LS Electric LSLV0022H100-2CONN(PLUS) Inverter VFD (H100+)

A three-phase input / three-phase output HVAC-tuned VFD from LS Electric’s H100+ series, featuring dedicated fan and pump control features plus built-in support for multiple building automation protocols.

The Polar Energy Assessment:

The LSLV0022H100-2CONN(PLUS) is designed for building services where motor control must integrate with HVAC systems. It supports advanced control modes, multiple communications protocols, and pump/fan-specific functions (like flow monitoring and auxiliary control). While it excels in indoor HVAC environments, its standard IP20 rating means it needs protection in harsher settings.

 

Pros

  • Designed for HVAC / pump & fan applications, with enhanced features.
  • Built-in communications: Modbus RTU, LS INV 485, BACnet MSTP, LonWorks, Metasys N2.
  • Dual-rating capability: supports both HD and ND motor ratings.
  • Overload tolerance: HD 150% (1 min), ND 120% (1 min).
  • Certifications: KC, CE, UL, cUL.

 

Limitations

  • External filtering may be needed
  • Default enclosure is IP20 / UL Type 1, so protection is required for dusty, wet, or outdoor environments.
  • Ambient limits are moderate; performance may require derating at higher altitude or temperature extremes.

Typical use cases

  • HVAC systems: chillers, air handlers, large fans, blowers.
  • Pump systems in commercial buildings and offices, water distribution in indoor setups.
  • Building automation installations requiring BACnet, Metasys, or LonWorks connectivity.
  • Avoid placing it in outdoor or uncontrolled environments unless adequately protected.

Reviews

There are no reviews yet.

Be the first to review “LS Electric LSLV0022H100-2CONN(Plus) Inverter VFD Low Voltage Drive”

Your email address will not be published. Required fields are marked *

Disclaimer

Product images are for illustrative purposes only and may not exactly match the actual item. All specifications and technical details should be verified using the official catalogs and datasheets provided by the respective manufacturer, as discrepancies may exist on this website.

Related products