LS Electric LSLV0022G100-2EONN Inverter VFD Low Voltage Drive

Parameter LSLV0022G100-2EONN
Model / Series LSLV0022G100-2EONN / G100 Series
Rated motor power HD: 2.2 kW (3.0 HP) · ND: 4.0 kW (5.4 HP)
Input voltage 3-phase 200–240 VAC (± tolerance)
Output 3-phase 200–240 VAC, variable 0–400 Hz
Rated output current HD: 11.0 A · ND: 12.0 A
Output frequency 0–400 Hz
Mounting Panel / cabinet mounting (side-by-side installation inside enclosure)
Enclosure / Protection IP20 (UL Type 1 optional)
EMC filter Not built-in in this variant
Communications Built-in: Modbus RTU / LS INV 485; Optional: EtherNet/IP, Profibus-DP, CANopen
Certifications / Standards KC, CE, UL, cUL
Ambient temp HD: –10 to +50 °C · ND: –10 to +40 °C
Dimensions (approx.) 101 × 177 × 150.5 mm (W × H × D)

Buy Now

Description

LS Electric LSLV0022G100-2EONN Inverter VFD (G100 — General Purpose Drive)

Mid-range three-phase-input / three-phase-output general-purpose inverter from LS Electric’s G100 line, supporting both constant and variable torque loads with advanced control options.

The Polar Energy Assessment:

The LSLV0022G100-2EONN is a solid choice when you need capability beyond micro drives but not full industrial frames. It handles motors up to 2.2 kW in Heavy Duty and 4.0 kW in Normal Duty, supports sensorless vector and V/f modes, and offers modular communication options. Because its default enclosure is IP20, it’s best used in protected cabinet environments. For harsher conditions, add a proper enclosure or select a variant with higher protection.

 

Pros

  • Dual-duty motor ratings (Heavy Duty and Normal Duty) for flexibility.
  • Supports V/f, slip compensation, sensorless vector control.
  • Built-in Modbus RTU / LS INV 485, with optional fieldbus modules (EtherNet/IP, Profibus-DP, CANopen, etc.).
  • Dimensions and footprint that fit well into control cabinets (Frame B).
  • Certifications: KC, CE, UL, cUL.
  • Overload capacity of 150 % for 1 minute (HD) / 120 % for 1 minute (ND).

 

Limitations

  • No builtin EMC filter in this variant, so external filtering may be necessary in EMI-sensitive environments.
  • Default IP20 rating, which offers little protection against dust, moisture, or environmental exposure.
  • Input current demands (11.8 A HD, 13.1 A ND) may require robust wiring and protection equipment upstream.

 

Typical use cases

  • Pumps, fans, and general motor control in factory or plant environments.
  • Conveyor systems, light-to-moderate machinery needing stable speed control.
  • OEM or panel integration where space, modular communications, and flexibility matter.
  • Not ideal for outdoors or dusty, wet, or unprotected installations without additional enclosure.