LS Electric LSLV0008H100-2CONN(Plus) Inverter VFD Low Voltage Drive

Parameter LSLV0008H100-2CONN(PLUS)
Model / Series LSLV0008H100-2CONN(PLUS) (H100+ Series)
Rated motor power HD: 0.4 kW (0.5 hp) · ND: 0.75 kW (1.0 hp)
Input voltage 3-phase 200–240 VAC (single-phase 240 VAC supported for ND)
Output 3-phase 200–240 VAC, variable 0–400 Hz
Rated output current Output Current (HD): 2.5 A · (ND): 5.0 A (3-phase input)
Output frequency 0–400 Hz
Mounting Panel / enclosure mounting — side-by-side / wall mounting inside control cabinet (refer to drawing)
Enclosure / Protection IP20 standard; UL Type 1 optional cover
EMC filter options may be required depending on site
Communications Built-in: Modbus RTU, LS INV 485, BACnet/MSTP, LonWorks, Metasys N2. Optional: RAPIEnet+, EtherNet/IP, Modbus TCP, BACnet/IP
Certifications / Standards KC, CE, UL, cUL
Ambient temp HD: −10 to 50 °C · ND: −10 to 40 °C (derate to operate up to +50 °C)
Dimensions (approx.) Frame A — W × H × D: 160 × 232 × 181 mm (6.30 × 9.13 × 7.13 in)

Buy Now

Description

LS Electric LSLV0008H100-2CONN(PLUS) Inverter VFD (H100+ — Fan & Pump Drive)

HVAC-focused low-voltage variable frequency drive (H100+ series) from LS Electric, optimized for fan and pump control with built-in HVAC communications and extended control features for energy-efficient systems.

The Polar Energy Assessment:

The LSLV0008H100-2CONN(PLUS) is a compact 1-HP class VFD tuned for HVAC and pump/fan applications. It offers robust fan/pump control features, multiple fieldbus options, and a practical set of I/O (including 5 relay outputs), making it a strong choice for commercial building automation and OEM panels where protocol compatibility and HVAC functions matter. If you need a drive for heavy industrial torque spikes or harsh outdoor duty without enclosure upgrades, look at a ruggedized alternative.

Pros

  • HVAC & pump optimized: H100+ includes fan/pump-specific functions for energy savings and system control.
  • Good control range: V/f control (IM/PM) plus slip compensation for stable motor behavior.
  • Reasonable overload capability: HD 150% for 1 min / ND 120% for 1 min — helps withstand transients.
  • Built-in communications for building networks: Modbus RTU, LS INV 485, BACnet/MSTP, LonWorks, Metasys N2 (with Ethernet/fieldbus options).
  • Multiple relay outputs and convenient I/O: reduces need for extra option cards in many HVAC installs.

Limitations

  • Standard enclosure IP20 (UL Type 1 optional); not suitable for dusty/wet/outdoor environments without additional protection.
  • EMC filter and DC reactor are not listed as built-in in the datasheet (variant dependent); external filtering may be required in sensitive sites.
  • Intended for HVAC/fan/pump and similar loads; not aimed at extreme heavy-inertia industrial drives.

Typical use cases

  • Ideal for HVAC systems; fans, blowers and chillers in commercial buildings.
  • Pumps in water treatment or building services where BACnet/Metasys/LonWorks connectivity is needed.
  • OEM equipment and compact control panels requiring built-in relay outputs and multiple protocol support.
  • Less ideal for outdoor, unprotected installations or for long-term continuous heavy-torque motors without derating and enclosure upgrades.