MMP

Smart Electronic Motor Protection Relay

• Current, Voltage, Power Measurement, and Power Factor Protection
• Instantaneous interruption compensation and restarting
• Harmonic measurement (1st to 16th)
• Modbus communication and 4~20mA

Features

Convenience
  • Comprehensive digital motor protection relay with the MCU (microprocessor control unit)
  • Applicable to inverter circuits
  • Function to store the cause(s) of failure/fault
  • One-body type and separate body type
  • Communication function (RS485 modbus and 4~20ma output)
  • A wide range of reset functions
  • Date information display
  • Password setting
  • Total operating time and operating time setting
  • Wide setting of ground fault current sensitivity 30ma~25a
 
Reliability
  • Thermal heat build-up inverse time/inverse time/definite time selection function
  • Wide setting range and dual protection
  • The device may be used without external CT up to 100A, providing convenience and cost-effective solution
  • Various motor starting modes
  • Metering of current, voltage, and energy (with 1% accuracy for A & V)
  • Carries out complex relay functions related to current, voltage, energy, and power factor
  • Self-diagnosis and sequence monitoring
  • Power loss and restarting
  • Frequent-starting protection

Specification

Function
Range
Accuracy(%)
Remarks

Voltage (V)

0.00V~9999V

±1.0%

Phase1 : Phase voltage,

Phase3 : Line voltage

Current (A)

0.00V~9999V

±1.0%

Phase current

Zero-phase current (In)

0.00V~9999V

±3.0%

Reverse current (I2)

0.00V~9999V

±3.0%

Active power (W)

0.000W~999.9MW

±1.0%

Forward

Reactive power (VAR)

0.000W~999.9MVAR

±1.0%

Forward

Active power amount (WH)

0.000W~999.9MWH

±1.0%

Reactive power amount (WVARH)

0.000W~999.9MVARH

±1.0%

PF

-1.00~1.00

±0.03

cosθ

Voltage hamonics (%)

0~100%

±5.0%

2nd -16th odd harmonics

Current hamonics (%)

0~100%

±5.0%

2nd -16th odd harmonics

Rating
Specification
Communication number1~247
Baud rate9600, 19200, 38400 bps
Communication ParityNone, Even, Odd
Stop Bit1bit (fixed)
Communication data swapOFF / ON (Limited to float, long data of 0x04 (Read Input Registers))
Operation modeDifferential
Communication distanceMax. 1.2km
CableRS-485 Shielded Twist 2-Pair Cable
Transmission MethodHalf-Duplex–
Max. In/Output Voltage

-7V~+12V