MMP

Smart Electronic Motor Protection Relay

• Current, Voltage, Power Measurement, and Power Factor Protection
• Instantaneous interruption compensation and restarting
• Harmonic measurement (1st to 16th)
• Modbus communication and 4~20mA

Features

Convenience
  • Comprehensive digital motor protection relay with the MCU (microprocessor control unit)
  • Applicable to inverter circuits
  • Function to store the cause(s) of failure/fault
  • One-body type and separate body type
  • Communication function (RS485 modbus and 4~20ma output)
  • A wide range of reset functions
  • Date information display
  • Password setting
  • Total operating time and operating time setting
  • Wide setting of ground fault current sensitivity 30ma~25a
 
Reliability
  • Thermal heat build-up inverse time/inverse time/definite time selection function
  • Wide setting range and dual protection
  • The device may be used without external CT up to 100A, providing convenience and cost-effective solution
  • Various motor starting modes
  • Metering of current, voltage, and energy (with 1% accuracy for A & V)
  • Carries out complex relay functions related to current, voltage, energy, and power factor
  • Self-diagnosis and sequence monitoring
  • Power loss and restarting
  • Frequent-starting protection

Specification

FunctionRangeAccuracy(%)Remarks
Voltage (V)0.00V~9999V±1.0%Phase1 : Phase voltage,
Phase3 : Line voltage
Current (A)0.00V~9999V±1.0%Phase current
Zero-phase current (In)0.00V~9999V±3.0%
Reverse current (I2)0.00V~9999V±3.0%
Active power (W)0.000W~999.9MW±1.0%Forward
Reactive power (VAR)0.000W~999.9MVAR±1.0%Forward
Active power amount (WH)0.000W~999.9MWH±1.0%
Reactive power amount (WVARH)0.000W~999.9MVARH±1.0%
PF-1.00~1.00±0.03cosθ
Voltage hamonics (%)0~100%±5.0%2nd -16th odd harmonics
Current hamonics (%)0~100%±5.0%2nd -16th odd harmonics
RatingSpecification
Communication number1~247
Baud rate9600, 19200, 38400 bps
Communication ParityNone, Even, Odd
Stop Bit1bit (fixed)
Communication data swapOFF / ON (Limited to float, long data of 0x04 (Read Input Registers))
Operation modeDifferential
Communication distanceMax. 1.2km
CableRS-485 Shielded Twist 2-Pair Cable
Transmission MethodHalf-Duplex–
Max. In/Output Voltage-7V~+12V